Internal Channel

The Internal Channel configuration defines virtual field units that have several special internal purposes, including an ISaGRAF Field Unit, Status Field Unit, Virtual RTU, Segment field unit, or Internal Master. The Internal Channel configuration and its 'child' objects are similar in structure to the Master Channel and its 'child' objects, but they refer to internal databases rather than external devices being polled by a communication protocol.

AttributesFunction
Object TypeInternal Channel  
Parent(s)System → Clients → Master Channels 
Instance 0 to 15 (typically 15 is reserved for the Internal Channel, but instance 14 might also be used if a second ISaGRAF RTU is included) 
The Internal Channel must have at least Circuit child object defined under it. The Database Flush (DumpRTDB) object is an optional child under Internal Master (see page ). 

...

The ISaGRAF RTU (logic, I/O, and data) exists as a separate task inside the RediGate. Similar to an external RTU, the ISaGRAF RTU contains data. In order to get this data into an RTDB, it must be scanned by the Scan Table – even though it resides inside the same hardware. The reason for this is to have a consistent Channel structure for all RTUs. For a more complete explanation, see the section ISaGRAF 5-Internal Channel Functional Elements.

If the ISaGRAF RTU does not contain data that is necessary to store in an RTDB, then it is not necessary to define any polls to the ISaGRAF RTU. As one example, the ISaGRAF logic may be written with special ISaGRAF functions such as DMOV or ISAMOV to move data from ISaGRAF or an RTDB, or from one RTDB into another. Or, the ISaGRAF logic may simply act on data from other RTDB's, such as sending a Publish message or an E-mail. In these cases, the data contained within the ISaGRAF RTU may not need to be scanned by the Internal Channel in order to read it into the ISaGRAF RTDB, and thus no Scan Table rows need to be defined.

Also note that other units under the Internal Channel (Status RTU, Virtual RTU, Segment RTU) do not need to be polled for data. They reside under the Null Circuit, and their data simply appears in their own RTDBs automatically without being scanned.

Null Circuit

A Null Circuit object defines placeholder in the configuration, under which one or more Status/Control, Virtual, Segment, or Internal Master field units are defined for an Internal Channel.

...

PropertiesValues
Circuit Type 

Placeholder for the circuit type as 'Null Circuit'.

Virtual Field Unit

A Virtual Field Unit object allows an additional Real-time Database (RTDB) to be defined for internal storage of data. This may be used as a data repository for the ISaGRAF program logic to store data values, and/or the RTDB may serve as the source of data for a Slave Channel definition.

...

PropertiesValues
Unit Name

Enter the field unit name as an identifier for the Field Unit. 

Unit AddressEnter the Field Unit address. This should be a unique address from any other ISaGRAF, Status, or Internal Master field unit addresses on this Internal Channel. The default address is 3. 
ProtocolPlaceholder for field unit protocol type 'Repository Database Unit'.
Com RetriesThis parameter is a null field to retain compatibility with other field unit objects. The only option is 'N/A'. 
Comm Status  Holdreg

Enter the starting holding register to contain the communication status for this field unit. Typically, this field is unused for the Virtual Unit.

Each Comm Status takes 5 registers, beginning at the register configured in this parameter. The Comm Status Holdreg for each field unit in a configuration must be defined such that the five registers do not overlap other registers being used.

If the register is defined in the 30,xxx address range, the status values will be stored in the local device's RTDB (i.e., the RTDB defined as a child object to this ISaGRAF Field Unit.

If the register is in the 40,xxx range, the values will be stored in the Status/Control Field Unit RTDB.

The Comm Status Holdreg is optional, and can be set to 0 to disable the storage of status registers.

See the section Communication Status Registers5-Internal Channel, for a description of the five Comm Status Register contents. 

Produce RBEs

Select this option to determine whether to produce a Report by Exception (RBE) flag when data in this unit's RTDB changes.

In the RTDB, for every data point, there are potentially 4 RBE flags associated with every data point. When the data point changes, the RBE flags are set. These flags are used to determine when new data needs to be reported to the HCP. 

No PollsThis parameter is a null field to retain compatibility with other field unit objects. The only option is 'N/A'.

Internal Master Field Unit

The Internal Master is a special type of Field Unit which is designed to provide an easy mechanism for collecting and consolidating data from any other Field Unit RTDBs into the RTDB associated with the Internal Master unit. In theory, it operates like a Master Channel Field Unit, which polls data from an external device; but the Internal Master operates only to take data from one RTDB to another.

AttributesFunction
Object TypeFieldUnitInternalMast 
Parent(s)System → Clients → Master Channels → Internal Channel → NullCircuit
Instance

Must be between 0 and 256, and should be unique under this Null Circuit among all Status, Virtual, and Internal Master field units.

The Internal Master Field Unit should have a Modbus RTDB5-Internal Channel child object defined under it (see page ).   

PropertiesValues
Unit Name

Enter the field unit name.

Unit AddressEnter the field unit address. This should be a unique address from any other ISaGRAF, Status, Virtual, or Internal Master field unit addresses on the Internal Channel.  The default address is 5. 
Protocol

Select the Protocol type for the Internal Master field unit. The Protocol selection determines the rules by which a host can access the data in this Virtual Master's RTDB, via attachment to a Slave Channel. Available Protocol types are:

Read/Write Internal RTU, not to DBM. This allows a host to both read data from the RTDB and write data directly to the device configured in the Source Channel/RTU. Read/Only Internal RTU. This allows a host to read data from the RTDB, but writes are not allowed. Data in the RTDB can be changed by ISaGRAF or by Internal Master polls from other RTDB locations, but not by an external host connected via Slave Channel. R/W RTU or to DBM if no Remapped Poll Record. This allows a host to read data from the RTDB and write data directly to the device configured in the Source Channel/RTU if there are matching poll records; otherwise, write data is stored directly into this Internal Master's RTDB registers. 

Com RetriesEnter the number of communication retries after a failed poll attempt. If a poll attempt fails, poll will be sent again up to the configured number of "Com Retries" before the field unit is declared failed. 
Comm Status  HoldregEnter the starting holding register to contain the communication status for this field unit.  Each Comm Status takes 5 registers, beginning at the register configured in this parameter. The Comm Status Holdreg for each field unit in a configuration must be defined such that the five registers do not overlap other registers being used. 
If the register is defined in the 30,xxx address range, the status values will be stored in the local device's RTDB (i.e., the RTDB defined as a child to this Field unit).  If the register is in the 40,xxx range, the values will be stored in the Status/Control Field Unit RTDB. The Comm Status Holdreg is optional, and can be set to 0 to disable the storage of status registers. See the section Communication Status Registers5-Internal Channel, for a description of the five Comm Status Register contents. 
Produce RBEsSelect this option to determine whether to produce a Report by Exception (RBE) flag when data in this unit's RTDB changes. In the RTDB, for every data point, there are potentially 4 RBE flags associated with every data point. When the data point changes, the RBE flags are set. These flags are used to determine when new data needs to be reported to the HCP. 
Poll Table

Click the Edit Table button to define the Modbus polls to be sent to this unit. Note that the Poll Table only defines how the Modbus protocol is defined to operate for each set of data defined in the polls. The Poll Table doesn't actually do any of the polling itself. If you want any of these polls to be sent to the Field Unit on a regular basis, it should be referenced in one or more Scan Table entries in the Master Channel. 

Src Chan – Enter the Channel number of the RTDB containing the source data. This is either a Master Channel or Internal Channel instance number that must be defined under the Master Channels placeholder. 

Src RTU – Enter the Field Unit number of the RTDB containing the source data. This is the Unit Address configured in the properties of the field unit, not the instance number of the field unit ACE object, if they are different. 

Src Data – Enter the source register number for the starting register in the Field Unit's RTDB to begin retrieving data. 

Src Type - Enter the data type of the data being requested. See below for a discussion of Src Type options in the Master Channel. 

Src Count – Enter the number of registers to retrieve. The maximum number allowed in any poll is the same as for Modbus polls: 2000 Boolean registers, 125 registers of 16-bit type, or 62 registers of 32-bit type.  The Count includes the number of register values being requested, starting at the Src Data register. 

Dest Data – Enter the starting destination register within this Internal Master's RTDB to place the polled data. Ensure that there is a large enough quantity of registers in the RTDB to store the count. The destination register type should be chosen based on the Source Format of the data.  Booleans should be stored into Boolean RTDB registers. 16-bit values should be stored into 16-bit RTDB registers. 32-bit values or 16-bit pair values should be stored into 32-bit RTDB registers 
When reading data from internal databases, the Internal Master also reads the quality flag status for each point, and individually sets the quality flags on the destination data to match the source point status. 

 


Discussion on Source Type

Several Src Type options are provided in the Internal Master Field Unit. These provide a number of unique capabilities for copying and transforming data from one RTDB location to another.
The following table gives a list of the Internal Master Src Type options, and an explanation of how they are used.

...


The POD object in the ACE configuration holds a set of programming instructions which can be used to manipulate or make decisions on data stored in RTDBs. Up to 9999 POD modules can be configured per Internal Master Channel, which are called by a Poll Table of an Internal Master RTU (which in turn is triggered by a Scan Table entry in the Internal Master Channel).

Status Field Unit

A Status Field Unit object may be used to contain unique information for internal communication diagnostics. Field units defined under Master Channels and the ISaGRAF field unit contain a parameter for storing communication status (Comm Status Register). If the Comm Status Register for any Field Unit is configured with a starting address in the 40,xxx address range, its status values are stored in the RTDB defined for this Status Field Unit. This allows all communication status information to be stored in one place, if desired in the system design.

However, if the Comm Status Register for any Field Unit is defined with a starting address in the 30,xxx address range, the communication status values for that device are stored in the RTDB for that Field Unit rather than the common Status Field Unit RTDB. In that case, the Status Field Unit is not necessary and may be omitted from the configuration.

See the section Communication Status Registers 5-Internal Channel for a description of the communication status registers stored for Field Units.

...


The Status Field Unit should have a Modbus RTDB 5-Internal Channel child object defined under it (see page ).

PropertiesValues
Unit Name

Enter the field unit name as an identifier. 

Unit AddressEnter the field unit address. This should be a unique address from any other ISaGRAF, Virtual, or Internal Master field unit addresses on the Internal Channel. Typically this address is set to 2. 
ProtocolPlaceholder for field unit protocol type 'System Control & Status Unit'. 
Com RetriesThis parameter is a null field to retain compatibility with other field unit objects. The only option is 'N/A'. 
Comm Status  HoldRegThis parameter is a null field to retain compatibility with other field unit objects. It should be set to 0. 
Produce RBEsSelect this option to determine whether to produce a Report by Exception (RBE) flag when data in this unit's RTDB changes. In the RTDB, for every data point, there are potentially 4 RBE flags associated with every data point. When the data point changes, the RBE flags are set. These flags are used to determine when new data needs to be reported to the HCP. 
No PollsThis parameter is a null field to retain compatibility with other field unit objects. The only option is 'N/A'.
Communication Status Registers

The section Status Field Unit 5-Internal Channel describes the Status Control RTU, which stores communication statuses for field units. The five status values contain the following data for each unit:

...

The RTDB for the Status/Control field unit must include an adequate number of holding registers to contain all the Comm Status registers for all defined Field Units, and these 5 Comm Status registers for each device must not overlap each other.

Segment Field Unit

 

A Segment Field Unit object allows Segment databases (RTDB) to be defined with a more flexible structure than most RTDBs. Like the Virtual unit, the Segment Field Unit is simply a data repository and does not require any Internal Channel scans to be defined. The Segment unit is used to create a more granular list of registers with a mix of different data types.

AttributesFunction
Object TypeFieldUnitSegment 
Parent(s)System → Clients → Master Channels → Internal Channel → NullCircuit
Instance

Must be between 0 and 255, and should be unique under this Null Circuit among all Status, Virtual, and Internal Master field units. 
The Segment Field Unit should have a Segment RTDB5-Internal Channel child object defined under it. 

PropertiesValues
Unit Name

Enter the field unit name as an identifier for the Field Unit.

Unit AddressEnter the Field Unit address. This should be a unique address from any other ISaGRAF, Status, Virtual, or Internal Master field unit addresses on this Internal Channel. 
ProtocolPlaceholder for field unit protocol type 'Segment Database Unit'. 
No CommsUnused
Not Used Unused
No PollsUnused

 

Segment RTDB

 

A Segment RTDB (Real Time DataBase) defines the size of the virtual database reserved for the Segment Field Unit. The Segment RTDB contains some significant differences from other RTDB objects. It is more flexible in size and construction, and multiple Segment RTDBs may be configured under a single Segment Field Unit. The Segment RTDB also allows deadbands to be defined in the database by point number, rather than through a separate field-based Deadband object.

...

PropertiesValues
Produce RBEsSelect this option to determine whether to produce a Report by Exception (RBE) flag when data in this unit's RTDB changes. In the RTDB, for every data point, there are potentially 4 RBE flags associated with every data point. When the data point changes, the RBE flags are set. These flags determine when new data needs to be reported to an MQTT server, HCP, or other hosts supporting RBE. 
Database

Click the Edit Table button to edit the details of the RTDB definition.

Definition  Point Count – Enter the number of data points of this type to be allocated space in the database. Point Format – Select the point data format: UINT8 – Unsigned 8-bit integer (0 to 255) SINT16 – Signed 16-bit integer (-32,768 to 32,767) UINT16 – Unsigned 16-bit integer (0 to 65,535) SINT32 – Signed 32-bit long integer UINT32 – Unsigned 32-bit long integer REAL32 – IEEE floating point (32-bit) 
Deadband – Enter the deadband value for the points defined on this row, which is the amount a value in the RTDB can change before it will be flagged as an RBE. Deadband value is entered as an integer or floating point value, which is handled as a 15-character (max) string. If IEEE floating point format is used, its entry must include a decimal point (such as 11.0). 
Comment - Optional column, allowing a descriptive comment to be entered for each row in the table. The Comment field is unused in the configuration.

 

DirectorPOD

Elecsys provides a separate manual to describe how PODs are configured and to explain each of the many function codes available. See the RediGate POD Programming Manual for further instructions.

Virtual Circuit

A Virtual Circuit object defines an internal communications path to one ISaGRAF field unit from an Internal Channel. The Virtual Circuit is simply a placeholder, designed to match the operation of a normal Async Circuit.

...

PropertiesValues
Circuit TypePlaceholder for circuit type of 'Virtual Circuit'.

 

ISaGRAF Field Unit

An ISaGRAF Field Unit object is used to run a protocol task that allows an ISaGRAF logic program to run in the RediGate, and defines parameters for how data is read from and written to the ISaGRAF unit.

The RediGate allows for running two independent ISaGRAF logic programs simultaneously. In this case, the Internal Channels should be defined as instance numbers 14 and 15, with each channel including a Virtual Circuit and ISaGRAF Field Unit objects. In either case, to allow the ISaGRAF Workbench program to download and monitor the ISaGRAF logic program(s), the ISaGRAF Field Unit definition must be attached to a Slave Channel definition. See the section Slave Channels 5-Internal Channel for setting up the Slave Channel.

...

The ISaGRAF Field Unit should have a Modbus RTDB 5-Internal Channel child object defined under it (see page ).

PropertiesValues
Unit Name

Enter the field unit name.

Unit name is displayed in diagnostic menus and in an HCP diagnostic screen. 

Unit Address

Enter the actual field unit address which will be used for the ISaGRAF Field Unit. This Modbus unit address will be referenced under a Slave Channel, from which the ISaGRAF workbench will communicate to the logic program. This should be a unique address from any other Status, Virtual, or Internal Master field unit addresses on the Internal Channel.

Valid addresses 1 to 255. Typically address 1 is used for one ISaGRAF unit (often configured in Channel 15), but if using two ISaGRAF RTUs in the same configuration one of them must be configured for address 123. 

ProtocolPlaceholder for the protocol type as 'IsaGraf Logic Unit'. 
Com RetriesEnter the number of communication retries after a failed poll attempt. If a poll attempt fails, it will try again up to the configured number of "Com Retries" before the field unit is declared failed. 
Holdreg

Enter the starting holding register to contain the communication status for this field unit.

Each Comm Status takes 5 registers, beginning at the register configured in this parameter. The Comm Status Holdreg for each field unit in a configuration must be defined such that the five registers do not overlap other registers being used.

If the register is defined in the 30,xxx address range, the status values will be stored in the local device's RTDB (i.e., the RTDB defined as a child object to this ISaGRAF Field Unit.

If the register is in the 40,xxx range, the values will be stored in the Status/Control Field Unit RTDB.

The Comm Status Holdreg is optional, and can be set to 0 to disable the storage of status registers.

See the section Communication Status Registers5-Internal Channel, for a description of the five Comm Status Register contents. 

Produce RBEsSelect this option to determine whether to produce a Report by Exception (RBE) flag when data in this unit's RTDB changes. In the RTDB, for every data point, there are potentially 4 RBE flags associated with every data point. When the data point changes, the RBE flags are set. These flags are used to determine when new data needs to be reported to the HCP. 
Poll Table

Click the Edit Table button to define the Modbus polls to be sent to this ISaGRAF field unit. Note that the Poll Table only defines how the Modbus protocol is defined to operate for each set of data defined in the polls. The Poll Table doesn't actually do any of the polling itself. If you want any of these polls to be sent to the ISaGRAF Field Unit on a regular basis, it should be referenced in one or more Scan Table entries in the Internal Channel. 

Source Register – Enter the source register in the ISaGRAF RTU to begin polling data. This will be a Modbus register defined on an I/O board definition in the ISaGRAF logic program. 
Source Format – Enter the data type of the data being requested. See below for a discussion of Source Format options.

See the section   Modbus/Open Modbus TCP Field Unit  for a full discussion on Source Formats. For the ISaGRAF RTU, typically the following Source Formats should be used:

Boolean – for boards defining Boolean data 16 bit register (HL) – for boards defining 16-bit data 32 Bit B/B Endian (HLhl) – for ISaGRAF boards defining 32-bit data 
Count – Enter the number of registers to poll. The maximum number allowed in any poll is 2000 Boolean registers, 125 registers of 16-bit type, or 62 registers of 32-bit type. The Count includes the number of entities being requested, based on the Source Format type listed above. For instance, if polling 10 sets of 32-bit data which occupy pairs of 16-bit registers (one of the "16 Bit Pair" types of data), the Count should be 10 for the number of entities (not 20 for the number of registers being requested). 
Destination Register – Enter the starting destination register within the RTDB (Real Time Data Base) to place the polled data. The Destination Register type should be chosen based on the Source Format of the data.  Booleans should be stored into Boolean RTDB registers. 16-bit values should be stored into 16-bit RTDB registers. 32-bit values or 16-bit pair values should be stored into 32-bit RTDB registers 
Comment - Optional column, allowing a descriptive comment to be entered for each row in the table. The Comment field is unused in the configuration.

 

Load/Store ISaGRAF Defaults

The Load/Store object defines a separate download file, containing parameter values used by the ISaGRAF STORE16 and STORE32 boards. The STORE boards are pseudo boards containing variables that are stored in the Flash file system (see the Elecsys ISaGRAF Manual for more details on these boards).

...

PropertiesValues
Parameter Table

Click the Edit Table button to edit the default values contained in the Load/Store parameter table.  

Parameter 1 through Parameter 16 – Enter the value for each parameter defined in the ISaGRAF STORE16 or STORE32 board. Multiple rows defined in the Parameter Table correspond to multiple sequential instances of the STORE boards (in the order of instances defined in the ISaGRAF application). 
Comment - Optional column, allowing a descriptive comment to be entered for each row in the table. The Comment field is unused in the configuration. 
When uploading the ACE configuration, the lsaabbcccc file will be created and uploaded separately at the same time.

 

TextStore Object

A TextStore object defines a separate download file in the configuration, containing default text strings which may be read and used by the ISaGRAF program logic. The TextStore file is created with the name staabbcccc, where aabbcccc is identical to the ISaGRAF file isaabbcccc to which it is attached.

...